Register offset
| Name
| Minimum value
| Maximum value
| Bits/ Sign
|
0
| Number of named alarms
| 99
| 256
| 16
|
1
| Emergency stop
| 0
| 15
| 13/16-16/16
|
| Low oil pressure
| 0
| 15
| 9/16-12/16
|
| High coolant temperature
| 0
| 15
| 5/16-8/16
|
| Low coolant temperature
| 0
| 15
| 1/16-4/16
|
2
| Under speed
| 0
| 15
| 13/16-16/16
|
| Over speed
| 0
| 15
| 9/16-12/16
|
| Generator Under frequency
| 0
| 15
| 5/16-8/16
|
| Generator Over frequency
| 0
| 15
| 1/16-4/16
|
3
| Generator low voltage
| 0
| 15
| 13/16-16/16
|
| Generator high voltage
| 0
| 15
| 9/16-12/16
|
| Battery low voltage
| 0
| 15
| 5/16-8/16
|
| Battery high voltage
| 0
| 15
| 1/16-4/16
|
4
| Charge alternator failure
| 0
| 15
| 13/16-16/16
|
| Fail to start
| 0
| 15
| 9/16-12/16
|
| Fail to stop
| 0
| 15
| 5/16-8/16
|
| Generator fail to close
| 0
| 15
| 1/16-4/16
|
5
| Mains fail to close
| 0
| 15
| 13/16-16/16
|
| Oil pressure sender fault
| 0
| 15
| 9/16-12/16
|
| Loss of magnetic pick up
| 0
| 15
| 5/16-8/16
|
| Magnetic pick up open circuit
| 0
| 15
| 1/16-4/16
|
6
| Generator high current
| 0
| 15
| 13/16-16/16
|
| Calibration lost
| 0
| 15
| 9/16-12/16
|
| Low fuel level
| 0
| 15
| 5/16-8/16
|
| CAN ECU Warning
| 0
| 15
| 1/16-4/16
|
7
| CAN ECU Shutdown
| 0
| 15
| 13/16-16/16
|
| CAN ECU Data fail
| 0
| 15
| 9/16-12/16
|
| Low oil level switch
| 0
| 15
| 5/16-8/16
|
| High temperature switch
| 0
| 15
| 1/16-4/16
|
8
| Low fuel level switch
| 0
| 15
| 13/16-16/16
|
| Expansion unit watchdog alarm
| 0
| 15
| 9/16-12/16
|
| kW overload alarm
| 0
| 15
| 5/16-8/16
|
| Negative phase sequence current alarm
| 0
| 15
| 1/16-4/16
|
9
| Earth fault trip alarm
| 0
| 15
| 13/16-16/16
|
| Generator phase rotation alarm
| 0
| 15
| 9/16-12/16
|
| Auto Voltage Sense Fail
| 0
| 15
| 5/16-8/16
|
| Maintenance alarm
| 0
| 15
| 1/16-4/16
|
10
| Loading frequency alarm
| 0
| 15
| 13/16-16/16
|
| Loading voltage alarm
| 0
| 15
| 9/16-12/16
|
| Fuel usage running
| 0
| 15
| 5/16-8/16
|
| Fuel usage stopped
| 0
| 15
| 1/16-4/16
|
11
| Protections disabled
| 0
| 15
| 13/16-16/16
|
| Protections blocked
| 0
| 15
| 9/16-12/16
|
| Generator breaker failed to open
| 0
| 15
| 5/16-8/16
|
| Mains breaker failed to open
| 0
| 15
| 1/16-4/16
|
12
| Bus breaker failed to close
| 0
| 15
| 13/16-16/16
|
| Bus breaker failed to open
| 0
| 15
| 9/16-12/16
|
| Generator reverse power alarm
| 0
| 15
| 5/16-8/16
|
| Short circuit alarm
| 0
| 15
| 1/16-4/16
|
13
| Air flap closed alarm
| 0
| 15
| 13/16-16/16
|
| Failure to sync
| 0
| 15
| 9/16-12/16
|
| Bus live
| 0
| 15
| 5/16-8/16
|
| Bus not live
| 0
| 15
| 1/16-4/16
|